A partial discharge detection method for SF6 insulated inverted current transformers adopting inner shield case as UHF sensor

  • Junhao Li
  • , Xuanrui Zhang
  • , Xutao Han
  • , Xiu Yao

Research output: Contribution to journalArticlepeer-review

39 Scopus citations

Abstract

A partial discharge (PD) detection method for SF6 insulated inverted current transformers (SIICTs) adopting an inner shield case as an ultra-high frequency (UHF) sensor is proposed in this paper. The inner shield case is a component of the SIICT. Its structure is similar to that of an antenna and can be used as a UHF sensor to measure the PD UHF signal. A 110 kV current transformer is used as an experimental object and the voltage standing-wave ratio of the inner shield case is calculated. The validity and sensitivity of this method are proved by experiments with ac voltage. This PD detection method solves the problem that the UHF sensor is difficult to mount inside current transformers and provides a novel method for PD detection of SIICTs.

Original languageEnglish
Article number8295142
Pages (from-to)3237-3239
Number of pages3
JournalIEEE Transactions on Power Delivery
Volume33
Issue number6
DOIs
StatePublished - Dec 2018

Keywords

  • Partial discharges
  • UHF
  • gas insulated inverted current transformers
  • live detection
  • shield case