Skip to main navigation Skip to search Skip to main content

Case Study on the Activation of Low-Voltage Protection Devices

  • Zhejiang University
  • University Co.

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

Abstract

Three incidents of low-voltage protective device activation are analyzed: low power factor and excessive harmonic content in lighting circuits causing breaker tripping, incorrect residual current device wiring leading to drain pump circuit failure to close, and aging wire insulation causing frequent residual current device tripping. Based on an overview of low-voltage protection devices activation, the process of on-site investigation, cause analysis, and relatively optimal solutions are presented.

Original languageEnglish
Title of host publication2025 4th International Conference on Power System and Energy Technology, ICPSET 2025
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages272-276
Number of pages5
ISBN (Electronic)9798331501587
DOIs
StatePublished - 2025
Event4th International Conference on Power System and Energy Technology, ICPSET 2025 - Chengdu, China
Duration: Jul 18 2025Jul 20 2025

Publication series

Name2025 4th International Conference on Power System and Energy Technology, ICPSET 2025

Conference

Conference4th International Conference on Power System and Energy Technology, ICPSET 2025
Country/TerritoryChina
CityChengdu
Period07/18/2507/20/25

Keywords

  • automatic transfer switch
  • circuit breaker
  • earth leakage current
  • harmonics
  • low-voltage electrical apparatus
  • power factor
  • residual current device

Fingerprint

Dive into the research topics of 'Case Study on the Activation of Low-Voltage Protection Devices'. Together they form a unique fingerprint.