Abstract

This paper evaluates the impact of pressure drop in server racks on the cooling of the IT equipment. The measured impedance curves for servers internal resistance, rack doors, and Cable Management Arms (CMA) are used to estimate the reduction in the cooling airflow rate. In this study, 1 RU and 2 RU servers, and a 9 RU server simulator are used as representative IT equipment. A Computational Fluid Dynamics (CFD) model is used to investigate the influence of the rack structure on the thermal field. The effect of the cooling air flow rate on the temperature of the server's internal components is also studied experimentally.

Original languageEnglish
Title of host publicationThermomechanical Phenomena in Electronic Systems -Proceedings of the Intersociety Conference
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages547-556
Number of pages10
ISBN (Electronic)9781479952670
DOIs
StatePublished - Sep 4 2014
Event14th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2014 - Orlando, United States
Duration: May 27 2014 → May 30 2014

Publication series

NameThermomechanical Phenomena in Electronic Systems -Proceedings of the Intersociety Conference

Conference

Conference14th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, ITherm 2014
Country/TerritoryUnited States
CityOrlando
Period05/27/14 → 05/30/14

Keywords

  • CFD
  • Data center
  • cable management arm
  • perforated doors
  • pressure drop
  • rack structure
  • server resistance