Abstract
With the increasing penetration of inverter-based resources (IBRs), inverter control methods, including grid-following (GFL) and grid-forming (GFM) control, dominate power-system dynamics. Differences between these control strategies introduce complex interactions that significantly affect system stability and performance. This paper aims to elucidate the mechanisms of control-loop coupling and inverter-level participation in hybrid systems. Our contributions include: 1) A dynamic relative gain array (DRGA)-based method is developed to quantify frequency-dependent coupling between any specified control loops of GFL and GFM inverters; 2) A low-rank block DRGA is devised to identify inverters involved in interactions in large-scale IBR grids by capturing dominant interaction modes while preserving inverter participation ranking; 3) A port-Hamiltonian based control method, which encodes the inverter controller structure, is designed to suppress the interactions under varying operating conditions without incurring new instability issues. Experimental results verify the interaction analysis.
| Original language | English |
|---|---|
| Journal | IEEE Transactions on Industry Applications |
| DOIs | |
| State | Accepted/In press - 2026 |
Keywords
- dynamic relative gain array
- grid following
- grid forming
- Inverter interaction
Fingerprint
Dive into the research topics of 'Frequency-Dependent Interaction Identification and Suppression of GFM and GFL Inverters'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver